The MCS 021 heat emitter guide, and where it's used now

MCS 021, the Heat Emitter Guide for Domestic Heat Pumps, is a quick table that tells you whether a room's radiators or underfloor heating can work at a given flow temperature. It gives each combination a temperature star rating: more stars, lower flow temperature, better efficiency.

It is a screening check, not a design method, and the current design standard doesn't require it. Its star rating table lives on in MCS 031. Checked 31 October 2026.

How the table works

  1. Work out the room's heat loss per square metre (W/m²) and find its band: under 30, 30 to 50, 50 to 80, 80 to 100, 100 to 120 or 120 to 150.
  2. Pick the emitter: radiators (with an oversize factor), screed underfloor, or aluminium panel underfloor.
  3. Read across to the flow temperature you want. The cell gives the star rating, or for underfloor the widest pipe spacing that still heats the room.

A blank cell means that emitter can't heat the room at that flow temperature: reduce the heat loss or choose differently.

Underfloor heating in MCS 021

The underfloor tables assume 16 mm pipe and outputs worked out to BS EN 1264, at pipe spacings of 100, 150, 200, 250 or 300 mm. Three floor coverings are given:

CoveringThermal resistance
Tile0.00 m²K/W
Wood0.10 m²K/W
Carpet0.15 m²K/W (1.5 tog)

For rooms losing more than 100 W/m² the guide has no underfloor option at any flow temperature. There is no separate method for suspended timber floors beyond the aluminium panel build.

Radiators in MCS 021

Radiators are rated by oversize factor: the catalogue output at ΔT50 divided by the room heat loss. The bigger the factor, the lower the flow temperature the room can run at, and the more stars it gets. A blending valve adds 5 °C to the flow temperature the heat pump has to make.

MCS 021 today: MCS 031 Table 2

The current design standard, MIS 3005-D, doesn't reference MCS 021. But the same star rating table appears as the Heat Emitter Guide in MCS 031, the pre-sale performance estimate every MCS installer gives the customer. There it picks the efficiency (SPF) used to estimate running costs, from the heat loss band and the flow temperature.

Do it with the free tool

The free tool reads the MCS 021 underfloor table for every room, so it shows the widest pipe spacing that works for the floor build, covering and flow temperature, or warns when underfloor can't heat the room.

Frequently asked questions

What is MCS 021?

The Heat Emitter Guide for Domestic Heat Pumps (Issue 2.1, 2015): a table of star ratings and underfloor pipe spacings by room heat loss and flow temperature.

Is MCS 021 still required?

MIS 3005-D no longer references it. Its star rating table is used through MCS 031 Table 2 for the customer's performance estimate.

What pipe spacing does underfloor heating need for a heat pump?

It depends on the room's heat loss per m², the floor build, the covering and the flow temperature. MCS 021 gives the widest spacing that works, from 100 mm to 300 mm.

What tog rating does carpet have in MCS 021?

MCS 021 uses 0.15 m²K/W for carpet, which is 1.5 tog.

Related guides

Sources: MCS 021 Heat Emitter Guide for Domestic Heat Pumps, Issue 2.1 (May 2015); MCS 031 Heat Pump Pre-sale Information and Performance Calculation; MCS MIS 3005-D Issue 3.0. Checked 31 October 2026. Free Heat Pump Design follows the MCS method but is not an MCS product and is not endorsed by MCS. Check designs against MCS MIS 3005-D and the official MCS Heat Pump Calculator.