Heat pump noise and the MCS 020(a) calculation

Heat pump noise decides whether an air source unit can go in without planning permission. Since 29 May 2025, an air source heat pump in England only counts as permitted development if it passes MCS 020(a): 37.0 dB(A) or less at every neighbouring window and door. It replaced the old MCS 020, which had a 42 dB(A) limit and a background noise step.

Here is the method, the formula and what to do if it fails: the same check our free heat pump design software runs for each neighbouring window. Checked against MCS 020(a) Issue 1.1 on 31 October 2026.

What changed from the old MCS 020

  • The limit fell from 42 to 37 dB(A).
  • Background noise is no longer used.
  • Measured distances to 0.1 m replace the old rounded-up table.
  • Hedges and planting no longer count as a barrier.
  • There is a method for two units.

The five inputs

  1. Assessment positions: 1 m out from the middle of every door and window of a habitable room (living or sleeping) at each neighbouring property, every side and every floor.
  2. Sound power level (Lw) from the product fiche, energy label or MCS product data. Not the sound pressure figure, and not a low noise mode figure.
  3. Directivity (Q) from the reflecting surfaces within 1 m of the unit that extend at least 1 m past it: one surface Q2, two Q4, three Q8. More than three is a fail.
  4. Distance (r) in a straight line from the centre of the unit to the assessment position, to 0.1 m.
  5. Barrier attenuation, from the table below.
BarrierNo viewPartial viewFull view
Masonry, or solid fence 18 mm or thicker, no gaps10 dB5 dB0 dB
Solid fence under 18 mm, no gaps5 dB2.5 dB0 dB
Gappy fence, hedge, poorly kept wall0 dB0 dB0 dB

The formula

Sound pressure Lp = Lw + 10 × log₁₀(Q ÷ 4πr²) − barrier attenuation

Round to 0.1 dB. It passes if every assessment position is 37.0 dB(A) or less. With two units, add their results at each position logarithmically: 10 × log₁₀(10^(L1/10) + 10^(L2/10)).

Example: Lw 58 dB(A), against one wall (Q2), 5.0 m away, no barrier. 10 × log₁₀(2 ÷ (4π × 25)) = -21.96, so Lp = 58 - 21.96 = 36.0 dB(A) to 0.1 dB. A pass.

If it fails

Move the unit, pick a quieter model, add a qualifying barrier, or apply for planning permission. A fail means it isn't permitted development, so installing it without permission risks enforcement. Give the customer a copy of the calculation, and redo it if anything on site changes.

Permitted development in England in 2026

  • Up to two units on a detached house, one on other houses and flats.
  • Outdoor unit up to 1.5 m³ on a house (0.6 m³ on flats).
  • No 1 m boundary rule any more.
  • Not on a pitched roof, not in the curtilage of a listed building, and in conservation areas not on a wall or roof facing a road.

Wales changed its rules from 1 June 2026 and also uses MCS 020(a). Scotland and Northern Ireland have their own rules: check locally.

Do it with the free tool

The free tool runs the MCS 020(a) check for each neighbouring window as you enter it: distance, reflecting surfaces and barrier, with the worst position and the pass or fail shown against 37.0 dB(A).

Frequently asked questions

How loud is an air source heat pump?

It depends on the model's sound power level and where it sits. What MCS 020(a) checks is the sound pressure at the neighbours' doors and windows, which must be 37.0 dB(A) or less. For example, a unit with a sound power level of 58 dB(A) against one wall, 5.0 m away with no barrier, gives 36.0 dB(A): a pass.

What is the MCS 020 noise limit?

37.0 dB(A) under MCS 020(a), measured 1 m from every door and window of a habitable room at neighbouring properties. MCS 020(a) replaced the old MCS 020 on 29 May 2025, which had a 42 dB(A) limit and a background noise step.

Does MCS 020(a) still use background noise?

No. The background noise step was removed, along with the urban and rural adjustment.

Do I need MCS 020(a) if I'm not MCS certified?

If you rely on permitted development in England, yes: the unit must meet MCS 020(a) whether or not the installation is MCS certified.

Is the 1 metre boundary rule still in force?

Not in England. It was removed on 29 May 2025, so the noise calculation now does that job.

Related guides

Sources: MCS 020(a) Issue 1.1 (14 April 2025); MCS 020 consultation response (November 2024); Town and Country Planning (General Permitted Development) (England) Order 2015, Schedule 2 Part 14 Class G as amended by SI 2025/560. Checked 31 October 2026. Free Heat Pump Design follows the MCS method but is not an MCS product and is not endorsed by MCS. Check designs against MCS MIS 3005-D and the official MCS Heat Pump Calculator.